 |
 |
 |
 |
 |
 |
|
 |
 |
|
 |
Q: What is the best material to use for column pipe in warm
(70°F and above) seawater?
A: It is universally accepted that a chemical composition
of nickel, aluminum, bronze equal to ASTM 148B Ca 958 has superior
corrosion resistance in seawater. When combined with its natural
resistance to the accumulation of biomass, (no hypochlorite injection
required) it is an easy choice.
Q: Why limit N.A.Brz to warm seawater?
A: That was not the intent. N.A.Brz is at least equal to or
superior to Ferrilium, Duplex SS, 316 SS, type 2 Ni-resist or
any of the cold water (North Sea) popular materials when compared
mechanically or for corrosion resistance. Up untill now, (before
the availability of Badenoch Bronze) these materials were less
expensive than N.A.Brz. For example: the Navies ot the world
use N.A.Brz exclusively.
Q: If that is true, why isn't N.A. Brz more
universally used?
A: That's easy! COST. A lot of the platform projects we work
on do not expect to be in service beyond five years. It is difficult
therefore to convince the owners, let alone the engineering company
responsible for limiting the capital expenditure of the platform,
to budget the use of N.A.Brz. However based on the amount of
column pipe service we are aware of, through our various service
technician contractors, N.A.Brz might be more cost effective
than is realized. The additional cost for the Fire Pump Co's
Badenoch Bronze will pay for itself twice over the first time
the pump is pulled.
Q: What is Badenoch Bronze?
A: Simply put, it is a fabricated N.A.Brz. Column pipe that
is considerably more economical to produce than cast Ca 958.
This column pipe when used with Ca 958 bearing retainers, rubber
bearing inserts, 316 SS shaft, couplings, and bolting is very
competitive to baked on phenolic epoxy coated carbon steel or
fiberglass. If 500 Monel lineshaft with 400 Monel couplings and
bolting are planned to be used with the carbon steel or fiberglass,
then the overall cost addition to the whole package is even less
significant.
Badenoch bronze is also more economical than 316 SS column pipe.
That is especially true when the cost and corrosive effect of
Hypochlorite injection (to reduce Biomass accumulation) is factored
into the equation. See the Badenoch Bronze detailed properties
Bulletin.
Q: Why does FPCo object to the use of column pipe centralizers?
A: The design intent of a vertical turbine pump is that the
impellers hang (like a plumb bob on a string) on the lineshaft.
It should, when at rest and at full speed, never touch the fluted
rubber bearings. The purpose the lineshaft bearings serve is
to stabilize the shaft during startup. As an example; if you
spin the plumb bob on the string you will note the string will
knot-up. The same thing happens to the lineshaft when starting
torque is applied, the shaft distorts. The bearings are there
to minimize the distortion. The shaft straightens out when it
reaches operating speed (Un-winds) and thrust load is applied.
With that in mind, no side load should be exerted on the column
pipe that might cause the bearings to bind or attempt to bend
the lineshaft. If the lineshaft is so affected the pump will
vibrate, or wear out the bearings causing the lineshaft to fail,
or break the quill (hollow) shaft in the driver or cause the
bearings in the driver to fail.
When you consider that the FPCo service technicians have never
seen a straight casing for a purnp to be installed on an oil
production platform, it is easy to understand why we do not recommend
centralizers.
Q: Why do you object to the use of fiberglass column
pipe?
A: Fiberglass column pipe has virtually no lateral dynamic strength.
That is why the manufactures require centralizers every 6M (20').
The centralizers then force the pump to bend to the contour of
the casing (there is no such thing as a straight caisson) causing
the pump to vibrate because the lineshaft is not allowed to hang
straight. There are a number of installations around the world
where this scenario has been played out. In some cases the solution
was to stiffen the pump discharge head or counter balance the
frequencies to mask the problem.
Q: How do cold ambient air temperatures impact the pneumatic
control and operating systems?
A: The NFPA-20 code prescribes that the machine
be maintained in an atmosphere of at least 40°F. Atmospheric
temperatures below this level require a heated enclosure, or
other means, to prevent malfunctions due to the cold. The engine
is equipped with a jacket water heater, the salt-water pumpage
is unlikely to freeze, the fuel tank must be heat traced, and
air does not freeze if it is dry. Assuming there is not a heated
enclosure, cold temperature impacts the pneumatic control and
operating systems in the following manner:
1) Saturated utility air will freeze up all the components
in the engine starting system. Instrument air @ -40°C dew
point (minimum required air supply for the controller) should
be used exclusively. Minus 60°C will virtually eliminate
any problem.
2) Saturated air (which cannot be used in the controller under
any circurnstances) requires that all of the equipment in contact
with the starting air system be heat traced. This includes
the vessel, the piping to the start system, the regulator,
start valve and starter. Heat tracing is expensive and active
in order to provide the desired result and therefore is not
recommended. "Instrument air only" by comparison
is inexpensive and passive.
3) NFPA-20 requires the start system vessel to have sufficient
capacity to crank the engine for 180 seconds @ 40°F (4.45°C)
without make-up. As the temperature drops below 40°F the
effective vessel capacity is being reduced exponentially. Continuous
cranking will reduce the reclaimable cranking energy by considerably
more.
The FPCo system is designed to operate in temperatures below
40°F and still provide the cranking capacity required by
the code plus an additional safety margin. Empirical tests
have demonstrated that the design criterions used have a safety
factor of approximately 1.33 @ 40°F.
Q: How do cold ambient air temperatures impact an alternate
medium like methane gas when used for control and operating?
A: First the Methane gas alternate starting media must be dry
(7-lb/mcf) pipeline quality. Essentially the only difference
is the .843 specific gravity of the gas would effect (reduce)
all the capacities and all the major vents would have to be
connected to a flare stack. Heat tracing is dependent on the
severity of the cold and the dryness of the gas.
|
|
 |
 |
|
 |
|
 |
 |
|
 |